Security Sales and Integration Magazine

Fire/Life Safety

NFPA Recommends Draining Antifreeze in Residential Sprinklers

July 07, 2010 | Comments (0) | Post a comment

The National Fire Protection Association (NFPA) has issued a safety alert recommending that residential fire sprinkler systems containing antifreeze should be drained and the antifreeze replaced with water.

The alert follows a research study and an initial set of fire tests conducted after a fire incident raised concerns about antifreeze solutions in residential sprinkler systems. The incident involved a grease fire in a kitchen where a sprinkler with a high concentration of antifreeze deployed. The fire resulted in a single fatality and serious injury to another person.

"Fire sprinklers are one of the most effective ways to save lives and property from fire," says NFPA President James M. Shannon. "Until we can provide further information based on additional research that is currently underway, we are urging the public to continue the use of sprinklers but to follow our interim safety guidelines by removing antifreeze if it is in their sprinkler systems.

Shannon said based on testing conducted, 70/30 percent glycerin and 60/40 percent propylene glycol antifreeze may provide an unacceptable risk of harm to occupants in certain types of fire scenarios, in particular kitchen grease fires. There were successful tests where kitchen grease fires were extinguished or contained with a 50/50 percent glycerin solution but it was felt there should be additional testing to more fully understand if there is a risk associated with 50/50 percent glycerin solution.

Until the results of further testing on antifreeze are available, NFPA recommends the following:

  • If you have, or are responsible for, a residential occupancy with a fire sprinkler system, contact a sprinkler contractor to check and see if there is antifreeze in the system.
  • If there is antifreeze in the system, as an interim measure, drain the system and replace it with water only. Problems associated with freezing of sprinkler pipes can be mitigated by alternative measures such as insulation. NFPA hopes to provide further guidance based on additional testing before the winter freezing months.
  • If you are putting in a new residential sprinkler system, design and install a system that does not require antifreeze.

"We are providing this safety alert as interim guidance based on the information we have right now," says Shannon. "As soon as more information is available, we will update the public."

The NFPA Safety Alert Regarding Antifreeze in Residential Sprinklers and more information on this topic can be found at www.nfpa.org/antifreeze.

 


Request more info about this product / service / company

Read more about: NFPA, sprinkler systems

Review / Comment



Other Recent News

May 22, 2012

Eaton to Purchase Cooper Industries for $11.8B

Eaton Corp., a diversified industrial manufacturer, announced this week it has agreed to purchase Cooper Industries for $11.8 billion.

May 15, 2012

NFPA Seeks Code Enforcers for Technical Committees

The National Fire Protection Association (NFPA) has launched a recruitment campaign to increase the number of code enforcers participating on its technical committees.

April 24, 2012

Holland Township (Mich.) to Fine Offenders for False Fire Alarms

The Board of Trustees here approved a false fire alarm ordinance that will require repeat offenders to pay $750 for each false alarm.

April 10, 2012

SIA Supports Reintroduced Residential CO Poisoning Prevention Act

The Security Industry Association (SIA), in conjunction with several other groups, is supporting bipartisan legislation reintroduced by Congressman Jim Matheson (D-Utah) and Congressman Charlie Bass (R-N.H.) to increase the use of life-saving residential carbon monoxide (CO) alarms.

March 22, 2012

NICET Completes Transition to Computer-Based Test

The National Training Center (NTC) has completed the transition to computer-based testing (CBT) for NICET Fire Alarm exams.

Sign up for the eControl Panel

env Sign up here to receive current news and industry updates delivered right to your inbox.