Understanding the Basics of Arc & Ground Fault Circuit Interrupters

Over the years, AFCI and GFCI devices have been developed to further the NEC’s mission of preventing fires and electrocution, but how much do you really know about them?

Understanding the Basics of Arc & Ground Fault Circuit Interrupters

In September, I covered some of the requirements that are found within NFPA 70, National Electrical Code (NEC) as it relates to fire alarm installations.

This issue let’s continue within the NEC, with a discussion about fire alarms and the role of arc fault circuit interrupters (AFCI) and ground fault circuit interrupters (GFCI).

Two of the primary reasons for the NEC are the prevention of fires through arcing and the prevention of electrocution. Over the years, AFCI and GFCI devices have been developed to further those causes, but how much do you really know about them? It’s good to understand the basics.

Current Shutoff Prevents Damages & Death

A GFCI is installed so as to detect an imbalance between the load or hot conductor and the neutral conductor. When the circuit is normal, the currents between these two conductors should be the same.

If there is a difference in currents, this may indicate the presence of a short circuit. This may be an indication that current is passing through a body. A GFCI will trip within 25 to 40 milliseconds if there is a change of the current between 5 and 30 milliamps (mA).

Upon the trip, the current will be cut off, preventing the possibility of electrocution. The quick trip time is to thwart even a small current from causing a person’s heart to go into ventricular fibrillation, which can lead to death. A current of even 30 mA can be fatal. It is not the voltage that kills, but the current.

An AFCI, on the other hand, is designed to detect an electric arc, or discharge, and shut down the circuit when an arc is sensed. An AFCI recently prevented a fire at my home when a bedside lamp started to arc.

Before I had time to get to the plug, the circuit powering the lamp was de-energized. So I can tell you the AFCI worked, and that’s why I’m covering that here instead of, say, the value of an NFPA 13-D sprinkler system.

Keep in Mind Usage Restrictions

Both AFCI and GFCI devices can be prone to false trips. Because of this, there are exceptions within the NEC outlining instances when AFCI and GFCI devices are not to be used for circuits that provide power to either smoke alarms or fire detection systems within a residence.

Section 210.8 within NFPA 70 has the requirements for ground fault circuit interrupters. Section 210.12 covers arc fault circuit interrupters. Both of these sections refer the user to 760.121(B), Branch Circuit, which stipulates:

The branch circuit supplying the fire alarm equipment(s) shall supply no other loads. The location of the branch-circuit overcurrent protective device shall be permanently identified at the fire alarm control unit. The circuit disconnecting means shall have red identification, shall be accessible only to qualified personnel, and shall be identified as “FIRE ALARM CIRCUIT.” The red identification shall not damage the overcurrent protective devices or obscure the manufacturer’s markings. This branch circuit shall not be supplied through ground fault circuit interrupters or arc fault circuit interrupters.

The last sentence of that paragraph offers the aforementioned restriction that GFCI and AFCI devices shall not be used on the branch circuit that is providing power to fire alarm equipment. This also goes for those circuits that provide power to smoke alarms.

So why is this? These circuits are dedicated to their use, so that no other devices or equipment is to be powered from them. The general conclusion is that there may be a momentary event that would cause a false trip, thus powering down the fire alarm system or the smoke alarms.

While there should be an indication on a fire alarm system that there is no longer 120VAC, this may not be the case for a smoke alarm. For a residential dwelling unit, the occupier of the space may not be aware that their smoke alarms are no longer powered, especially if they happen to miss hearing the low battery chirp.

This is debated during every cycle of the NEC’s Code Making Panel 3 since I have been a member. In the end, while GFCI and AFCI are extremely important, the restrictions to them remain for fire alarm equipment circuits.

In November we’ll take a break from the NEC and focus on the latest alarm industry technology and products. I’m heading to Essen, Germany, and will report my findings from the big Essen 2018 Expo.

If you enjoyed this article and want to receive more valuable industry content like this, click here to sign up for our FREE digital newsletters!

About the Author

Contact:

Shane Clary, Ph.D., is Security Sales & Integration’s “Fire Side Chat” columnist. He has more than 37 years of security and fire alarm industry experience. He serves on a number of NFPA technical committees, and is vice president of Codes and Standards Compliance for Pancheco, Calif.-based Bay Alarm Co.

Security Is Our Business, Too

For professionals who recommend, buy and install all types of electronic security equipment, a free subscription to Commercial Integrator + Security Sales & Integration is like having a consultant on call. You’ll find an ideal balance of technology and business coverage, with installation tips and techniques for products and updates on how to add to your bottom line.

A FREE subscription to the top resource for security and integration industry will prove to be invaluable.

Subscribe Today!

Leave a Reply

Your email address will not be published. Required fields are marked *

Get Our Newsletters